OSSD Wiring Guide: Pinout, PNP vs. NPN Polarity, and Safety Relay Integration
A OSSD Wiring Guide illustrates how to wire a dual channel safety output (OSSD1 and OSSD2) to a safety relay or safety PLC across 1 to 300 m runs. Both channels source 24 V during normal operation and go to 0 V within 10 to 20 ms when tripped. 150 us to 1 ms dark test pulses run every 100 to 200 ms to catch wire shorts automatically.
What Is an OSSD Output? How Dual-Channel Test Pulses Detect Wiring Faults

An Output Signal Switching Device (OSSD) is the solid-state switching circuit inside a safety light curtain, laser scanner, or interlock switch. It uses two redundant semiconductor channels (OSSD1 and OSSD2) that are powered at 24 V DC and go to 0 V when a guard zone is breached.
What does OSSD mean in machine safety? The abbreviation OSSD defines a pair of solid-state channels of electronics. Two OSSD channels work in parallel, thus a single hardware fault cannot defeat safety function. Under EN IEC 61496-1:2020 Clause 4.2.4 and Clause 5.2.8, electro-sensitive protective equipment (ESPE) must detect every single-point electrical fault automatically. Standard 24 V switching outputs cannot detect a signal wire pinched against a +24 V conductor in a tray. If that short circuit happens on a non-safety sensor, the programmable logic controller reads a permanent HIGH signal. Even if an operator enters the hazardous press zone, the machine continues operation.
To avoid this failure cause, OSSD safety components deploy two independent channels labeled OSSD1 and OSSD2. Each channel uses its own central processing unit or a comparator logic gate to self-monitor output state. If the field of view is clear, both OSSD1 and OSSD2 provide 24 V DC to the safety controller. If something breaks the beam or power is lost, both OSSD channels go to 0 V.
How do safety controllers test wire integrity without stopping the machine?
Safety sensors test wire integrity during active production by injecting brief 0 V dark test pulses into the 24 V OSSD lines. According to industrial OSSD electrical operation data, these test pulses occur at intervals of 0.5ms to 10ms or up to 200 ms. Downstream safety relays and safety controllers use 10-20ms input filters, so sub-millisecond 0 V dips never trip the machine.
During each test phase, the sensor’s built-in microcontroller opens one high-side transistor for a fraction of a millisecond. It then reads the output pin voltage through an internal feedback loop. As shown in DigiKey’s oscilloscope waveform analysis of SICK and Banner light curtains, each signal stays active high at 24 VDC. It dips to 0 VDC once every 200 ms. The two channels are out of phase with a heartbeat period of 100 ms between OSSD1 and OSSD2.
Because OSSD1 and OSSD2 pulse at staggered timestamps, the built-in feedback comparator spots any cross-wire short immediately. Let’s say OSSD1 shorts to OSSD2 within a crushed cordset. The test pulse from OSSD1 then bleds to OSSD2 at the wrong millisecond. Both channels immediately latch into a 0 V fault state and cut power to the machine actuators.
We summarize the exact waveform behavior for normal and faulted states in the 4-Fault OSSD Pulse Diagnostic Matrix below.
| Wiring State / Fault Mode | OSSD1 Waveform | OSSD2 Waveform | Internal Comparator & Safety Controller Action |
|---|---|---|---|
| Normal Safe State (Beam Clear) | 24 VDC with 0 VDC pulse every 200 ms | 24 VDC with phase-offset 0 VDC pulse (100 ms offset) | Both safety channels remain CLOSED; machine runs normally. |
| Fault 1: Short to +24 VDC Supply | Clamped at continuous 24 VDC (0 VDC dip missing) | Drops to 0 VDC after comparator detects missing dip | Sensor locks out within one pulse cycle; safety relay opens. |
| Fault 2: Short to 0 VDC / Ground | Clamped at continuous 0 VDC | Forced to 0 VDC by internal dual-channel logic | Safety controller detects discrepancy or dual-low state; machine stops. |
| Fault 3: OSSD1 Cross-Shorted to OSSD2 | Shows both OSSD1 and OSSD2 test pulses | Shows synchronous pulse bleed across channels | Phase comparator detects cross-talk; both outputs latch OFF at 0 VDC. |
| Fault 4: Open Circuit / Severed Wire | 0 VDC at downstream safety input terminal | 24 VDC at sensor, pulled to 0 VDC on fault | Downstream input drops immediately; discrepancy timer locks out restart. |
Standard OSSD Pinout and Wire Color Codes: 5-Pin vs. 8-Pin M12 Connectors

Standard A-coded 5-pin M12 receiver cables connect Pin 1 to +24 V (Brown), Pin 2 to OSSD1 (White), and Pin 3 to 0 V (Blue). Pin 4 is connected to OSSD2 (Black), and Pin 5 is connected to Functional Earth (Gray). 8-pin M12 connectors add External Device Monitoring (EDM) and reset interlocks.
When wiring a safety light curtain, the emitter and receiver usually do not share the same pin count. Only the receiver unit contains the OSSD output transistors. As documented in industrial safety light curtain wiring guides, standard optical pairs use an Example 2: Emitter with 3-pin, Receiver with 5-pin connector layout. Hardwired optical sync pairs use an Example 1: Emitter and Receiver with 7-pin Connectors layout.
Regardless of the number of connector pins, always power the sensor from a dedicated 24V SELV/PELV supply. As the wiring rule states, use only DC 24V power — never connect AC power. Applying 120 V AC control power directly to an M12 sensor plug will destroy the semiconductor output stage instantly.
| M12 Pin # | 5-Pin M12 Wire Color (IEC 60947-5-2) | 5-Pin Receiver Function | 8-Pin M12 Wire Color (IEC 60947-5-2 / DIN 47100) | 8-Pin Receiver Function |
|---|---|---|---|---|
| Pin 1 | Brown (BN) | +24 VDC Supply Voltage | White (WH) or Brown (BN) | OSSD1 or +24 VDC (See Datasheet) |
| Pin 2 | White (WH) | OSSD1 Safety Output 1 (24 VDC PNP) | Brown (BN) or White (WH) | +24 VDC Supply Voltage |
| Pin 3 | Blue (BU) | 0 VDC Common Reference | Green (GN) | Restart / Reset Interlock or Muting Lamp |
| Pin 4 | Black (BK) | OSSD2 Safety Output 2 (24 VDC PNP) | Yellow (YE) | EDM (External Device Monitoring) Input |
| Pin 5 | Gray (GY) or Green/Yellow | Functional Earth (FE) / Sync | Gray (GY) | OSSD1 Safety Output 1 (24 VDC PNP) |
| Pin 6 | Not Present | N/A | Pink (PK) | OSSD2 Safety Output 2 (24 VDC PNP) |
| Pin 7 | Not Present | N/A | Blue (BU) | 0 VDC Common Reference |
| Pin 8 | Not Present | N/A | Red (RD) | Functional Earth (FE) / Shield / Auxiliary |
Limitation & Field Caution: Wire colors on M12 open-end cables vary between IEC 60947-5-2 cordsets and legacy DIN 47100 or North American automotive cables. Pin number verification on the connector face always takes precedence over wire insulation color. Although IEC standards standardize 4-pin and 5-pin sensor colors, 8-pin cordsets frequently swap Brown and White between Pin 1 and Pin 2.
Match the molded numbers (1 through 5 or 1 through 8) stamped on the M12 insert face with the terminal schematic of your multi-beam safety sensor or light curtain receiver, prior to crimping ferrules onto open leads. Also bond the cable shield to the cabinet ground to alleviate electromagnetic interference.
PNP Sourcing vs. NPN Sinking OSSD Wiring: Polarity Rules and Common 0V Reference

Modern EN IEC 61496-1 Type 4 safety products mandate dual PNP sourcing OSSD outputs, because PNP transistors switch the Positive 24V rail. If a damaged wire touches a grounded machine steel, a PNP output fails safe to 0V and stops the machine. Legacy NPN sinking outputs switch the 0V path, so a chassis ground fault can mimic an active ON signal.
Polarity regulates fault behavior for several reasons. For instance, let’s look at the terminal voltages for each state. As defined in the industrial OSSD electrical operation specifications, when the safety device is in the SAFE state, the OSSD outputs are energized at 24V. When the safety device detects an intrusion or fault, it de-energizes both outputs to 0V.
In a PNP sourcing circuit, the safety controller’s input terminals (S12 and S22) act as current-sinking loads referenced to 0V. In contrast, an NPN sinking output pulls a pre-energized load down to 0V when active. Under OSHA 29 CFR 1910.217(b)(8)(v) and IEC 60204-1, industrial control systems use a grounded 0V PELV secondary. They must prevent any single ground fault from causing false machine operation.
If an NPN wire chafes against a grounded press frame, that ground connection completes the 0V sinking path permanently. A PNP sourcing OSSD shorted to the grounded frame drops to 0V immediately. The internal current limiter trips, and both channels lock out safely.
Modern PNP OSSD circuits also use multi-voltage internal comparators to catch cross-shorts instantly. According to European Patent EP3358592B1, the supply voltage sits at 24 V. Meanwhile, internal reducers step the first channel voltage down to 23 V and the second channel voltage down to 22 V. Cross-coupled PNP comparator transistors monitor this 1 V differential continuously. If either terminal shorts to the 24 V supply rail, the comparator detects the voltage jump and opens both switches to 0 V.
| Electrical Parameter | PNP Sourcing OSSD (Industry Standard) | NPN Sinking Output (Legacy / Non-Safety) |
|---|---|---|
| Switching Transistor Topology | High-side P-channel MOSFET / PNP transistor | Low-side N-channel MOSFET / NPN transistor |
| Safe State (Clear) Terminal Voltage | 24V DC actively sourced on OSSD1 and OSSD2 | Pulled down to 0V DC (current sinking to ground) |
| Tripped State (Interrupted) Voltage | 0V DC (high impedance pulled low by input load) | Floats high toward +24V DC via load pull-up |
| Wire-to-Chassis Ground Fault Result | Fails safe (clamped to 0V DC; machine stops) | Unsafe fault (mimics active 0V ON state) |
| Safety Relay / Safety PLC Compatibility | Directly compatible with IEC 61496-1 Type 4 inputs | Incompatible with positive-switching F-DI modules |
Never combine PNP and NPN outputs on the same safety relay. Never wire an external pull-up or pull-down resistor to an OSSD line to invert its logic. In addition, the 24 V DC supply powering the sensor and the 24 V DC supply powering the safety controller must share a bonded 0V common reference terminal. Without a shared 0V reference busbar, the 24 V OSSD signals have no return path and the safety inputs will fault.
How to Wire OSSD1 and OSSD2 to a Safety Relay with EDM and Reset Feedback

To wire a dual-channel OSSD sensor to a safety relay, land OSSD1 on safety input S12 and OSSD2 on safety input S22. Bond both 0 V commons together on terminal A2. Leave the safety relay’s internal test pulse terminals (S11 and S21) unconnected, because the OSSD sensor supplies its own 24 V power and dark test pulses.
As shown in DigiKey’s evaluation of the Schneider Electric XPSBAT12A1AC safety module, an OSSD-compatible safety relay reaches PL e and Category 4 under ISO 13849-1. It also achieves a component reliability rating of MTTFd > 30 years. Reaching that EN ISO 13849-1 Category 4 level requires External Device Monitoring (EDM). The EDM loop proves that downstream contactors K1 and K2 physically open on every stop command.
On mechanical power presses, monitoring stopping performance is also a mandatory occupational safety and health rule. Under OSHA 29 CFR 1910.217(h)(5)(ii), the brake monitor allows a stopping time increase of at most 10 percent, or 10 milliseconds, whichever is longer. Wiring the mechanically linked NC auxiliary contacts of K1 and K2 into the EDM loop, prevents a new press stroke if a main contactor welds closed.
Refer to the 3-Point EDM Contactor Feedback Loop Check below, before energizing the safety relay:
- First, select contactors K1 and K2 with mechanically linked NC mirror contacts (terminals 21-22) under IEC 60947-4-1 Annex F so the auxiliary contacts cannot close if any main power pole welds shut.
- Second, route terminal S33 in series with the K1 NC contact, the K2 NC contact, and a manual reset button to terminal S34. Use an 8-pin sensor’s internal EDM and route +24 V through K1 NC and K2 NC to Pin 4.
- Third, measure the resistance of the K1 NC-K2 NC series chain with an ohmmeter when the chain is de-energized. Loop resistance must sit below 2 ohms when open, and the circuit must break within 20 ms when K1 and K2 pull in.
How do you restart a system after an OSSD fault versus a temporary beam break?
Restarting after a temporary beam break requires clearing the sensing field and pressing the manual reset button once OSSD1 and OSSD2 return to 24V. The safety relay looks for a trailing-edge 0V-to-24V-to-0V transition on S34 so an operator cannot tamper with the button by taping it down. In contrast, clearing an OSSD cross-short fault requires fixing the damaged cable and cycling the 24V DC power supply.
When the hazard zone is large, and a person can pass through the sensing field and enter the hazard zone, the safety relay should not be automatically reset. If this is the case, in accordance with EN IEC 61496-1 Annex A.8, the manual reset switch should be placed outside the hazard zone and in view of the protected area.
Connecting OSSD Outputs to a Safety PLC or Safety Controller: Test Pulse & Discrepancy Settings

When connecting OSSD outputs to a Safety PLC’s F-DI card or a safe drive STO input, disable the PLC’s test pulses. Leaving the test pulses on causes pulse collisions with the sensor’s OSSD dark pulses, which result in false channel lockouts.
As stated in the Beckhoff’s TwinSAFE EL1918 and EL1904 application note, standard safety inputs pair each input with a clocked output supplying a pulsed +24V. That pulse tests dry mechanical contacts for short circuits. Since a self-testing OSSD sensor already generates its own 24V signal and periodic 0V test pulses, enabling the PLC’s clock pulse creates asynchronous waveform collisions.
Safe motion drives and safety controllers specify strict timing windows for OSSD inputs. According to the Kollmorgen AKD2G safety drive installation manual, safe digital inputs SIN1 to SIN4 accept pulse widths T1 from 150 us to 1 ms. The required pulse period T2 spans from 100 ms to 1 s with non-overlapping channels. Meanwhile, test pulses on safe digital outputs (SOUT1 to SOUT4) run at T1 450 us to 550 us and T2 810 ms to 990 ms.
Limitation & Configuration Rule: Enabling the safety PLC’s internal clock test pulse generator on an F-DI channel wired to an OSSD sensor leads to pulse collisions and nuisance faults. In Siemens TIA Portal (ET 200SP F-DI), Allen-Bradley Studio 5000 (GuardLogix) or Beckhoff TwinSAFE, set the sensor supply to “External.” Then disable short-circuit test pulses on both input channels.
Use the 5-Step Safety Relay vs. F-DI Interface Selector below to correctly set your safety controller parameters:
| Configuration Step | Dedicated Safety Relay Module | Safety PLC Fail-Safe Digital Input (F-DI) | Safe Motion Drive Dual-Channel STO |
|---|---|---|---|
| Step 1: Power Supply Source | Power OSSD sensor from external 24V DC (leave S11/S21 open) | Select “External Sensor Supply” in hardware configuration | Supply sensor from shared 24V PELV busbar |
| Step 2: Internal Test Pulses | Disable cross-short detection via dip switch if powered via S12/S22 | Disable PLC clocked test outputs (T0/T1 OFF) | Set STO input filter to accept 150 us to 1 ms OSSD pulses |
| Step 3: Channel Evaluation | Dual-channel 1oo2 evaluation (Equivalent / Active High) | 1oo2 (2v2) Equivalent evaluation mode | Dual-channel STO_A and STO_B simultaneous high |
| Step 4: Discrepancy Time | Fixed hardware window (50 ms to 500 ms) | Set software discrepancy timer to 50 ms – 100 ms | Set STO channel discrepancy tolerance to <= 100 ms |
| Step 5: EDM Feedback Path | Hardwired K1/K2 NC loop to S33-S34 reset terminal | Read K1/K2 NC auxiliary contact on standard DI + F-FB_EDM block | Read STO status word over FSoE / PROFIsafe or hardwired EDM |
Device-Specific OSSD Wiring: Safety Light Curtains vs. Safety Laser Scanners

While all electro-sensitive safety sensors output dual 24 V PNP OSSD signals, safety light curtains use separate emitter and receiver cables with optical or wire synchronization. Laser scanning devices, on the other hand, integrate the emitter, receiver, EDM and dynamic zone switching into a single multi-pin system plug.
Under EN IEC 61496-1:2020 and IEC 61496-2:2020, active opto-electronic protective devices (AOPDs) operate within the optical wavelength band of 400 nm to 1 500 nm. When installing a safety light curtain on a power press in Presence-Sensing Device Initiation (PSDI) mode, OSHA 29 CFR 1910.217(h)(9)(ii) sets a strict resolution limit. Light curtains used for PSDI operation must have a minimum object sensitivity no greater than 31.75 mm (1.25 inches).
Further, the response time of OSSD and the stopping time of the press sets a lower limit on the mounting distance of the sensor. Under OSHA 29 CFR 1910.217, minimum safety distance follows the equation Ds = Hs * (Ts + Tp + Tr + 2Tm) + Dp. In this formula, Hs is the hand speed constant of 63 inches per second (1.6 m/s). With every millisecond added to the OSSD relay turnaround time (Tr), the required mounting distance from the pinch point increases.
In the meantime, a safety laser scanner on an AGV uses Type 3 diffuse reflection (IEC 61496-3). Radio-frequency identification (RFID) non-contact interlocks and radar safety sensors also use dual OSSD channels, but add cascade inputs or multi-zone outputs.
| Device Category / Sensor Type | Application Scenario | Applicable Safety Standard | Connector & OSSD Channel Spec | Key Wiring Selection Rule |
|---|---|---|---|---|
| Type 4 Safety Light Curtain (Finger/Hand) | Hydraulic & mechanical power press point-of-operation | IEC 61496-1 & IEC 61496-2 (400 nm to 1 500 nm) | 3-pin Emitter + 5-pin or 8-pin M12 Receiver; 2x PNP OSSD | Keep sensitivity <= 31.75 mm for PSDI; wire K1/K2 EDM loop |
| Type 2 Safety Light Curtain (Body/Access) | Low-risk packaging & palletizer perimeter access | IEC 61496-1 & IEC 61496-2 (PL c / SIL 1) | 5-pin M12 Receiver; dual OSSD or single OSSD with test input | Match periodic test input to safety controller test output |
| Safety Laser Scanner (Stationary Cell) | Robotic welding cell & press brake area guarding | IEC 61496-1 & IEC 61496-3 (Type 3 / PL d) | 8-pin or 12-pin M12 system plug; 1 pair OSSD + 1 warning out | Separate non-safety warning output from OSSD1/OSSD2 pair |
| Safety Laser Scanner (Mobile AGV/AMR) | Autonomous mobile robot collision avoidance | IEC 61496-3 & ISO 3691-4 (PL d) | 12-pin or 17-pin M12; 2x OSSD pairs + encoder field inputs | Wire complementary dual-channel encoder inputs for zone switching |
| Multi-Beam Safety Light Grid (2 to 4 Beams) | Perimeter entry/exit guarding with muting | IEC 61496-2 Type 4 (PL e / SIL 3) | 5-pin or 8-pin M12; integrated muting sensor & lamp pins | Monitor muting lamp current to prevent dark-lamp fault lockout |
| Single-Beam Photoelectric Safety Sensor | Long-span access doors & automated storage aisles | IEC 61496-2 Type 2 / Type 4 | 4-pin M12 optical heads wired to DIN-rail evaluation unit | Terminate OSSD1/OSSD2 at central evaluation controller |
| RFID Non-Contact Safety Interlock Switch | Hinged & sliding machine guard doors (tamper resistant) | IEC 60947-5-3 & EN ISO 14119 Type 4 | 8-pin M12 pigtail; dual safety inputs (SI1/SI2) + dual OSSD | Use coded RFID actuators to prevent operator bypass or tamper |
| Safety Mat / Edge with OSSD Evaluation Unit | Tactile floor presence sensing around indexing tables | ISO 13856-1 / ISO 13856-2 | 4-wire resistive sensor into OSSD converter module | Convert 4-wire short-circuit loop into 24 V PNP OSSD pair |
| 3D Time-of-Flight / Safe Radar Sensor | High-dust, weld-spatter, or outdoor heavy machinery | IEC TS 62998-1 & ISO 13849-1 PL d | 8-pin M12 power/OSSD + 4-pin M12 Ethernet diagnostic port | Use shielded twisted-pair cable and bond functional earth |
In hybrid cells, engineers frequently pair a single-beam safety sensor or coded safety switches on access gates with an area scanner inside the cell. In all cases, auxiliary warning signals should be routed on separate conductors from safety rated OSSD1 and OSSD2 lines.
Series Wiring and Cascading Multiple OSSD Devices: Preventing Fault Masking Under ISO/TR 24119

Unlike dry mechanical E-stop contacts, standard OSSD semiconductor outputs cannot be wired in series by feeding OSSD1 of sensor A into the +24 V supply pin of sensor B. Cascading multiple OSSD devices requires sensors with dedicated dual safety inputs (SI1 and SI2), an active diagnostic node loop, or dedicated safety PLC inputs.
Limitation & ISO 14119 Rule: Direct daisy-chaining of standard OSSD outputs without individual node monitoring hides single-channel cross-faults (fault masking). That layout caps achievable diagnostic coverage under ISO/TR 24119. As shown in Compliance inSight Consulting’s analysis of ISO 14119:2024 Annex J, each contact may have a typical MTTFD of 80 years. However, opening and closing a healthy downstream guard in a passive series chain resets the safety relay and masks a welded upstream contact.
This fault-masking effect violates the EN ISO 13849-1 Category 3 and Category 4 requirement that every single fault must be caught at or before the next safety demand. When four or more passive interlocks are wired in series with frequent door openings, Diagnostic Coverage (DCavg) drops below 60% (Low). That drop caps the entire safety chain at PL c.
Can OSSD devices be daisy-chained across different manufacturers?
OSSD devices from different manufacturers can be daisy-chained when the downstream sensor provides dedicated OSSD-compatible safety inputs (SI1 and SI2). Its input filter must accept the upstream sensor’s test pulse width (T1: 150 us to 1 ms) and period (T2: 100 ms to 200 ms). If the pulse windows do not match, wire each sensor to a separate safety input pair or an active bus node.
To cascade multiple OSSD sensors while preserving category 4 / PL e diagnostic coverage and transmitting full diagnostic information to the HMI, two field proven architectures are:
- Active diagnostic nodes cascading over an M12 loop: as reported by Automation World on SICK Flexi Loop, active M12 loop nodes cascade up to 32 sensors with 30 meters per segment at PLe. Each node monitors its local sensor’s OSSD dark pulses independently. It then sends pin-level diagnostic information back to the safety controller.
- IO-Link Safety point-to-point wiring under IEC 61139-2: as reported in Pilz IO-Link Safety documentation, safe point-to-point communication achieves PL e (SIL 3) and stays independent of the upper fieldbus. Each OSSD device connects via an unshielded M12 cable to a master port, eliminating series fault masking completely.
When cascading OSSD sensors through SI1 and SI2 cascade inputs, keep in mind that turn-off delay is cumulative. Include the upstream sensor’s OSSD response time when calculating your safety distance per the OSHA 29 CFR 1910.217 safety standard.
Electrical Load Limits, Cable Capacitance, and Maximum Wire Length Calculations

The industrial sensor family OSSD safety circuit can be up to 100-300 meters. Two physical limits govern this length: DC loop resistance voltage drop (keeping terminal voltage at or above 21V under load) and line-to-ground RC cable capacitance. Excessive capacitance, among other things, rounds off microsecond dark test pulses and causes cross-short faults.
According to industrial OSSD specifications, OSSD outputs require a minimum of 21V at the device terminals under load. Standard industrial models allow up to 100-300m cable runs. However, under OSHA 29 CFR 1910.217(b)(8)(iii), DC control circuits must not exceed a nominal 240V d.c. rating. In practice, 24V DC PELV serves as the global standard safety voltage for OSSD devices.
Limitation & Capacitance Effect: Long unshielded multi-core cables with high line-to-ground capacitance round off sub-millisecond OSSD test pulses. That distortion prevents the sensor’s internal feedback comparator from seeing the 0 V state, before the pulse window expires. If the cable’s parasitic capacitance (C_cable) discharges slowly through the safety relay’s input impedance (R_load), OSSD1 stays above the low threshold during a 150 μs pulse window. The sensor misinterprets this slow RC decay as a short circuit to +24V DC and locks out.
Worked Engineering Calculation: 30-Meter M12 Cable Run (Voltage Drop & RC Pulse Distortion Check)
Consider wiring a Type 4 safety light curtain receiver over a 30 meters M12 cable segment (matching the 30 meters per segment benchmark). The run uses 22 AWG (0.34 mm²) shielded cable to feed a safety PLC F-DI input.
- In Step 1, calculate terminal voltage drop against the 21V minimum rule. A 22 AWG copper conductor has a resistance of 0.053 ohms per meter. Over a 30 meters run (60 meters round-trip loop) carrying 0.25 A total current, loop voltage drop equals 60 m * 0.053 ohms/m * 0.25 A = 0.80 V. With a 24V DC supply, receiver terminal voltage is 24.0 V – 0.80 V = 23.2 V, which safely exceeds the 21V minimum threshold.
- Step 2
Calculate the RC discharge time constant against OSSD pulse width T1. At 120 pF/m core-to-shield capacitance, a 30 meters cable adds 3.6 nF (3,600 pF) of line capacitance. Paired with a 3,000-ohm safety input impedance, the RC time constant (tau = R * C) equals 3,000 ohms * 3.6 nF = 10.8 microseconds.
- In Step 3, compare the 3*tau discharge window against the minimum 150 us pulse width. Full discharge below the 0V logic threshold takes 3 * tau = 32.4 microseconds. The 32.4 us decay is less than one-fourth of the minimum 150 us OSSD dark test pulse width in Kollmorgen’s OSSD timing table, therefore the pulse reaches 0V cleanly.
Troubleshooting OSSD Wiring Faults & Procurement Specification Checklist

Effective OSSD troubleshooting isolates whether a fault lockout is caused by optical beam misalignment, a missing 0V common bond, a test pulse colliding with a safety PLC, or an open EDM contactor loop. Measuring OSSD1 and OSSD2 with a standard digital multimeter cannot find pulse collisions, because the meter averages out dips less than a millisecond.
As shown in DigiKey’s two-channel oscilloscope diagnostic guide, every 200 ms, one of the two channels of the signal oscilloscope temporarily dips low. As shown in DigiKey’s two-channel oscilloscope diagnostic guide , each signal periodically dips low once every 200 ms. Connecting Channel 1 to OSSD1 and Channel 2 to OSSD2 immediately exposes missing test pulses or cross-channel coupling. For hardwired upgrades to smart diagnostics trunks, Pilz IO-Link Safety guarantees that safe, point-to-point communications reach the PL e level (SIL 3), while also live streaming fault codes to the PLC.
Finally, keep documented annual validation records for every press line. As stated in OSHA 29 CFR 1910.217(h)(10)(ii), any PSDI press safety system must be recertified and revalidated every 12 months. If a press passes 12 months without revalidation, it must be removed from PSDI service immediately.
What conditions must be met for an OSSD to maintain a safe ON state?
Four electrical and optical conditions must be satisfied for an OSSD pair to be in the safe 24 V ON state. The supply voltage at the terminals must be 21 V DC or more, and the protective sensing field must be unobstructed. In addition, the 0V dark test pulses on OSSD1 and OSSD2 must occur without cross-faults, and the EDM reset loop must close.
| Observed Symptom | Root Electrical Cause | Diagnostic Verification Method | Corrective Wiring Action |
|---|---|---|---|
| OSSD1 & OSSD2 Stuck at 0V (Beam Clear, Fault LED Flashing) | OSSD wire shorted to +24V DC or cross-shorted between Pin 2 and Pin 4 | Disconnect S12/S22 at relay and check continuity between Pin 2, Pin 4, and Pin 1 | Replace damaged M12 cordset and cycle 24V DC power to clear internal fault latch |
| Safety PLC F-DI Faults Every Few Seconds When Clear | PLC internal clock test pulse (T0/T1) colliding with sensor OSSD dark pulse | Inspect F-DI channel configuration in TIA Portal / Studio 5000 / TwinSAFE | Disable internal PLC test pulses on both channels; set discrepancy time to 50-100 ms |
| Safety Relay Trips on Long (>50 m) Cable Run | Cable capacitance rounding off 150 us – 1 ms test pulse or voltage drop below 21V | Scope OSSD1/OSSD2 at receiver vs. relay; measure DC voltage under load | Switch to low-capacitance cable, increase wire gauge, or shorten trunk below 30 m |
| Outputs Green on Sensor, Safety Relay K1/K2 Will Not Pull In | Open EDM loop (K1/K2 NC auxiliary contact stuck open) or floating 0V reference | Measure continuity across K1(21-22) and K2(21-22) in series with S33-S34 | Replace faulty force-guided contactor or bond sensor 0V (Pin 3) to relay A2 |
OSSD Safety Sensor & Wiring Harness Procurement Specification Checklist
Prior to submitting a Request for Quotation (RFQ) or finalizing your wiring schematic with CCH Shanghai Technology and Intelligence Co. Ltd., ensure the following seven specification items are reviewed:
- Specify EN IEC 61496-1 Type 4 (EN ISO 13849-1 Category 4 / PL e, SIL 3) or Type 2 (PL c / SIL 1) to match your machine risk assessment.
- Select dual-channel 24 VDC PNP sourcing OSSD outputs and check that pulse width (T1: 150 us to 1 ms) and period (T2: 100 ms to 200 ms) match your controller.
- Choose 5-pin M12 cordsets when an external safety relay manages EDM and reset, or select 8-pin / 12-pin M12 cordsets when using built-in EDM and restart interlock.
- Define the exact length of the cable run (standard 30 m / max 100 to 300 m) to ensure terminals voltage is at or above 21 V under full load.
- Stipulate that OSSD1 and OSSD2 land on a dedicated safety relay (S12 / S22), a Safety PLC F-DI card, or a safe drive STO input.
- Partner the sensor with force-guided K1/K2 contactors (IEC 60947-4-1) and check press stopping time to verify compliance with OSHA 29 CFR 1910.217 safety distance.
- Need pinout drawings, STEP CAD files, or application engineering review? Contact our team via the engineering contact page (custom cordset pricing and lead times are provided upon request).
Frequently Asked Questions
What does OSSD stand for in safety sensors?
OSSD stands for Output Signal Switching Device under EN IEC 61496-1 Clause 4.2.4. It is a dual-channel solid-state switching output included in a safety light curtain, a laser scanner, or a safety switch. Both channels source 24 V DC during normal operation and drop to 0 V DC within milliseconds whenever the protective field is interrupted.
Why do OSSD outputs use two channels (OSSD1 and OSSD2)?
OSSD outputs use two independent channels (OSSD1 and OSSD2) to satisfy EN ISO 13849-1 Category 3 and Category 4 (PL d and PL e) dual-channel redundancy rules. Each channel is driven by its own transistor and monitored by an internal comparator. If one transistor welds closed or one wire suffers a cross-fault, the second channel still de-energizes the safety relay and stops the machine hazard immediately.
Can I wire an OSSD output directly to a standard PLC digital input?
It is never permissible to wire OSSD output to only a standard, non-safety PLC digital input for personnel protection. A standard programmable logic controller uses a single-channel processor and has no certified cross-fault detection, input discrepancy timers, or force-guided output relays. You may only wire an auxiliary status to a standard PLC for HMI display after OSSD1 and OSSD2 terminate into a certified safety relay or fail-safe F-DI module.
How do I stop a Safety PLC from faulting when connected to an OSSD light curtain?
Disable the Safety PLC’s internal clock test pulse outputs on the two F-DI channels wired to OSSD1 and OSSD2. Then set the channel discrepancy timers to between 50 ms and 100 ms.
What is the difference between 5-pin and 8-pin M12 OSSD wiring?
A 5-pin M12 receiver cable carries +24 V (Pin 1), OSSD1 (Pin 2), 0 V (Pin 3), OSSD2 (Pin 4), and Functional Earth (Pin 5). It uses an external safety relay for EDM and reset. An 8-pin M12 connector provides wires for built-in EDM contactor feedback and restart interlock.
Why are OSSD outputs almost always PNP instead of NPN?
Industrial machine safety standards demand the use of PNP sourcing OSSD outputs because PNP transistors switch the positive 24 V rail. In a grounded 0 V PELV control circuit, per IEC 60204-1 and OSHA 29 CFR 1910.217, a pinched wire touching grounded machine steel on a PNP line drops to 0 V and immediately triggers a safe shutdown. On an NPN sinking circuit, the same ground fault completes the 0 V path and keeps the machine in an active ON state.
References & Sources
- CENELEC / IEC TC 44 – EN IEC 61496-1:2020 Safety of machinery – Electro-sensitive protective equipment – Part 1: General requirements and tests (Clauses 4.2.4, 5.2.8 & Annex A.2)
- U.S. Occupational Safety and Health Administration (OSHA) – 29 CFR 1910.217 Mechanical Power Presses: Control Circuits, Brake Monitors, and PSDI Safety Distance
- U.S. OSHA eTools – Machine Guarding: Presence-Sensing Devices and Muting Requirements
- European Patent Office (SICK AG) – EP3358592B1 Output Signal Switching Device (OSSD) with Multi-Voltage Cross-Short Detection
- DigiKey Engineering Forum – OSSD Safety Signals: What the Waveform Tells a Safety Relay (Oscilloscope Captures)
- Kollmorgen Technical Documentation – AKD2G Safe Motion Installation: OSSD Dark Test Pulse Timing Specifications (T1/T2)
- Beckhoff Automation USA – TwinSAFE EL1918 and EL1904: Test Pulses vs. OSSD Configuration
- Compliance inSight Consulting (Machinery Safety 101) —
Fault Masking in Series-Connected Interlocks under ISO 14119:2024 Annex J and ISO/TR 24119 - Automation World —
SICK Safety Controller with Flexi Loop: Cascading 32 OSSD Sensors at PL e - Pilz Automation —
IO-Link Safety Point-to-Point Communication up to PL e / SIL 3 (IEC 61139-2) - Industrial Monitor Direct Knowledgebase —
How OSSD Safety Outputs Work: Electrical Operation, Input Filters, and Cable Drop - Dadi / SICK Wiring Application Guide —
How to Wire a Safety Light Curtain: NPN vs. PNP Wiring Diagrams and Connector Pinouts